SOP for Cleaning of Cooling Coil

Purpose
To provide a documented procedure for Cleaning of Cooling Coil.

Objective
Cleaning of Cooling Coil.

Scope
This SOP is applicable for the Cleaning of the Cooling Coil at PharmaInfo Ltd.

Responsibility
Primary: Technician Engineering
Secondary: Manager Engineering

Procedure
  • Remove the main supply fuse & affix the label to “DO NOT START, MACHINE UNDER CLEANING”.
  • Switch the ‘OFF’ Air Handling Unit fan & chilled water valves.
  • Remove filters from Air Handling Unit.
  • Spray descaling chemical by pump on the fins of the cooling coil on both sides.
  • Clean cooling coil fins by water jet at 30 Ib/in2 from both sides.
  • Check for satisfactory cleaning by looking through the fins at the light source on the other side of the coil.